[Page 1] Siemens SIMOTION D425-2
SIMOTION SIMOTION D4x5-2 Manual Valid for SIMOTION D4x5-2, CX32-2, CBE30-2 and TB30 as of Version 4.4 04/2014 Preface Safety instructions 1 Description 2 Operator control (hardware) 3 Interfaces 4 Technical data of the ...
[Page 2] Siemens SIMOTION D425-2
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual b...
[Page 3] Siemens SIMOTION D425-2
Preface Content of the Manual This document is part of the SIMOTION D documentation package. Scope The SIMOTION D4x5-2 manual is valid for the SIMOTION D4x5-2 Control Units, as well as the supplementary CX32-2, CBE30-2 and TB30 system components. ...
[Page 4] Siemens SIMOTION D425-2
This documentation is included as electronic documentation in the scope of delivery of SIMOTION SCOUT. It comprises ten documentation packages. The following documentation packages are available for SIMOTION V4.4: ● SIMOTION Engineering System Ha...
[Page 5] Siemens SIMOTION D425-2
FAQs Frequently Asked Questions can be found in SIMOTION Utilities & Applications, which are included in the scope of delivery of SIMOTION SCOUT, and in the Service&Support pages in Product Support: http://support.automation.siemens.com Te...
[Page 6] Siemens SIMOTION D425-2
● SIMOTION SCOUT online help ● For additional documentation, see the Overview of SIMOTION documentation (separate document) Preface SIMOTION D4x5-2 6 Manual, 04/2014 ...
[Page 7] Siemens SIMOTION D425-2
Table of contents Preface.........................................................................................................................................................3 1 Safety instructions....................................................
[Page 8] Siemens SIMOTION D425-2
4.5 Power supply...............................................................................................................................64 4.6 Ethernet interfaces................................................................................
[Page 9] Siemens SIMOTION D425-2
7.4.3 Safety information.....................................................................................................................112 7.4.4 Interface description.............................................................................
[Page 10] Siemens SIMOTION D425-2
...
[Page 11] Siemens SIMOTION D425-2
Safety instructions 1 1.1 Fundamental safety instructions 1.1.1 General safety instructions DANGER Danger to life due to live parts and other energy sources Death or serious injury can result when live parts are touched. ● Only work on electri...
[Page 12] Siemens SIMOTION D425-2
WARNING Danger to life from hazardous voltage when connecting an unsuitable power supply Touching live components can result in death or severe injury. ● Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV (Protective...
[Page 13] Siemens SIMOTION D425-2
WARNING Danger to life due to fire spreading if housing is inadequate Fire and smoke development can cause severe personal injury or material damage. ● Install devices without a protective housing in a metal control cabinet (or protect the ...
[Page 14] Siemens SIMOTION D425-2
WARNING Danger to life when safety functions are inactive Safety functions that are inactive or that have not been adjusted accordingly can cause operational faults on machines that could lead to serious injury or death. ● Observe the info...
[Page 15] Siemens SIMOTION D425-2
NOTICE Damage through electric fields or electrostatic discharge Electric fields or electrostatic discharge can cause malfunctions through damaged individual components, integrated circuits, modules or devices. ● Only pack, store, transport and...
[Page 16] Siemens SIMOTION D425-2
WARNING Danger as a result of unsafe operating states resulting from software manipulation Software manipulation (e.g. by viruses, Trojan horses, malware, worms) can cause unsafe operating states to develop in your installation which can lead to d...
[Page 17] Siemens SIMOTION D425-2
1. Unintentional movements of driven machine components during commissioning, operation, maintenance, and repairs caused by, for example: – Hardware defects and/or software errors in the sensors, controllers, actuators, and connection technology...
[Page 18] Siemens SIMOTION D425-2
For more information about residual risks of the components in a drive system, see the relevant sections in the technical user documentation. 1.2 Specific safety information for SIMOTION D4x5-2 WARNING Danger to life from hazardous voltage when co...
[Page 19] Siemens SIMOTION D425-2
NOTICE Higher operating temperature if ventilation clearances are too small The 80 mm clearances above and below the components must be observed. The unit protects itself from overheating by shutting down. The ventilation clearance is measured fr...
[Page 20] Siemens SIMOTION D425-2
[Page 21] Siemens SIMOTION D425-2
Description 2 2.1 System overview Overview SIMOTION D is a drive-based version of SIMOTION based on the SINAMICS S120 drive family. With SIMOTION D, the SIMOTION PLC and motion control functionalities as well as the SINAMICS S120 drive software ...
[Page 22] Siemens SIMOTION D425-2
Typical applications include: ● Compact multiple-axis machines ● High-performance applications with short machine cycles ● Compact machines – Including the complete machine control in the drive – With extensive connection possibilities for ...
[Page 23] Siemens SIMOTION D425-2
The SIMOTION D4x5‑2 control units and their CX32‑2, CBE30-2 and TB30 supplementary system components are described in the following. Note With the SIZER configuration tool, you can easily configure the SINAMICS S110/120 drive family includi...
[Page 24] Siemens SIMOTION D425-2
A SIMOTION D axis grouping generally consists of the following elements: ● SIMOTION D (Control Unit) (1) This unit contains the programmable runtime system of SIMOTION and the drive software of SINAMICS S120. In principle, SIMOTION D is capable ...
[Page 25] Siemens SIMOTION D425-2
2.2 System components Central components SIMOTION D4x5-2 communicates with automation components via the following interfaces: ● PROFIBUS DP ● Ethernet ● PROFINET IO ● DRIVE‑CLiQ (DRIVE Component Link with IQ) SIMOTION D features a SINAM...
[Page 26] Siemens SIMOTION D425-2
PROFIBUS DP The control unit can communicate with the following components via the PROFIBUS DP interfaces: Table 2-3 Components on PROFIBUS DP Component Function Programming device (PG/PC) ... configures, parameterizes, programs, and tests with ...
[Page 27] Siemens SIMOTION D425-2
Ethernet The control unit can communicate with the following components via the Ethernet interfaces or be embedded in an automation environment: Table 2-4 Components on the Ethernet Component Function Programming device (PG/PC) ... configures, para...
[Page 28] Siemens SIMOTION D425-2
Component Function Other PROFINET IO I/O devices Drive units with PROFINET IO interface ... convert speed setpoints into signals for controlling the motor and supply the power required to operate the motors. Gateways ● IE/AS-Interface link PN...
[Page 29] Siemens SIMOTION D425-2
Component Function TM120 Terminal Module 4 temperature sensors (KTY84‑130 or PTC) can be evaluated via the TM120 Terminal Module. The temperature sensor inputs are safely electrically separated from the evaluation electronics in the TM120 Tempe...
[Page 30] Siemens SIMOTION D425-2
2.3 I/O integration Note Note that not all modules in the ET 200 I/O family are approved for SIMOTION. Moreover, system-related functional differences can come into play when these I/Os or I/O systems are used on SIMOTION vs. on SIMATIC. For e...
[Page 31] Siemens SIMOTION D425-2
2.4 Representation of SIMOTION D425-2 DP and D435-2 DP The following figure shows the SIMOTION D425‑2 DP and D435‑2 DP with their interfaces and front panel elements (fault and status displays). 'LDJQRVWLFVEXWWRQ 6SDFHU 2SWLRQVO...
[Page 32] Siemens SIMOTION D425-2
Note SIMOTION D425‑2 DP and D435‑2 DP must be operated with a double fan/battery module for heat dissipation. Without this module, the Control Units will not start up and cannot be commissioned. Information on how to install the double fa...
[Page 33] Siemens SIMOTION D425-2
2.5 Representation of SIMOTION D425-2 DP/PN and D435-2 DP/PN The following figure shows the SIMOTION D425‑2 DP/PN and D435‑2 DP/PN with their interfaces and front panel elements (fault and status displays). 'LDJQRVWLFVEXWWRQ 6SDFHU...
[Page 34] Siemens SIMOTION D425-2
Note SIMOTION D425‑2 DP/PN and D435‑2 DP/PN must be operated with a double fan/battery module for heat dissipation. Without this module, the Control Units will not start up and cannot be commissioned. Information on how to install the do...
[Page 35] Siemens SIMOTION D425-2
2.6 Representation of SIMOTION D445-2 DP/PN and D455-2 DP/PN The following figure shows the SIMOTION D445‑2 and D455‑2 with its interfaces and front panel elements (fault and status displays). 'LDJQRVWLFVEXWWRQ 6SDFHU 2SWLRQVORW...
[Page 36] Siemens SIMOTION D425-2
Note SIMOTION D445‑2 DP/PN and D455‑2 DP/PN must be operated with a double fan / battery module for heat dissipation. Without this module, the Control Units will not start up and cannot be commissioned. Information on how to install the ...
[Page 37] Siemens SIMOTION D425-2
Note The information contained in each field of the type plate on your actual control unit may differ from that presented in this manual (for example, a later product version, approvals and marks that have not yet been granted, e.g. C-Tick, et...
[Page 38] Siemens SIMOTION D425-2
2.8 CompactFlash card 2.8.1 Usage and function of the CompactFlash Card The CompactFlash card (CF card) is inserted in the slot with the designation CF (X109 interface). &RPSDFW)ODVKFDUG '[ 2SHUDWLQJHOHPHQWVFRYHU...
[Page 39] Siemens SIMOTION D425-2
The SIMOTION Kernel (SIMOTION D4x5‑2 firmware) and the software used to control the drives (SINAMICS firmware) are contained on the CF card. The CF card is used for ● Backing up the technology packages and user data (programs, configuration data...
[Page 40] Siemens SIMOTION D425-2
list. You can find this list both in the documentation that comes with the SIMOTION SCOUT DVD under \1_Important\Germany\Kompatibilitaet\… and on the Internet ( http://support.automation.siemens.com/WW/view/en/18857317). Type plate information ...
[Page 41] Siemens SIMOTION D425-2
Available Z options / licenses for CF cards ● Axis licenses – Pxx POS license and number (e.g. P02 = 2x POS license) – Gxx GEAR license and number (e.g. G03 = 3 x GEAR licenses) – Cxx CAM license and number (e.g. C01 = 1x CAM license) ● Mul...
[Page 42] Siemens SIMOTION D425-2
Table 2-8 Machine-readable identification via 2D code Characteristic Characteristic (example) Order No. ("1P" identifier to identify the products) 6AU1400-2PA22-0AA0‑Z Serial number ("S" identifier, item number) T‑WOQB02934 Ha...
[Page 43] Siemens SIMOTION D425-2
Operator control (hardware) 3 3.1 Overview of operator control and display elements The following figure shows the arrangement of the operator control and display elements of a SIMOTION D445-2 DP/PN. 2SHUD WRUFRQWURO DQGGLVSOD\ HOHPHQW...
[Page 44] Siemens SIMOTION D425-2
/('GLVSOD\V &)FDUG LQVHUWHGLQWKH &)FDUGVORW 5HVHWEXWWRQ 6HUYLFHVHOHFWRUVZLWFK 0RGHVHOHFWRU VHJPHQWGLVSOD\ 'LDJQRVWLFVEXWWRQ ',$* Figure 3-2 Control and display elements of ...
[Page 45] Siemens SIMOTION D425-2
0RGHVHOHFWRUVZLWFK 6HUYLFHVHOHFWRUVZLWFK Figure 3-3 Selector switches for service and operating modes of the SIMOTION D4x5-2 NOTICE Damage from electrostatic discharge The rotary switch can be destroyed by static electricity. Opera...
[Page 46] Siemens SIMOTION D425-2
Table 3-2 Mode switch settings Meaning Explanations RUN SIMOTION D4x5‑2 processes the user program and the associated system services: ● Reading process image of inputs ● Execution of the user programs assigned to the execution system. ● Writ...
[Page 47] Siemens SIMOTION D425-2
Service selector switch The following table shows the possible positions of the service selector switch. The service selector switch positions are explained in the order in which they are arranged on the SIMOTION D4x5‑2. Table 3-3 Switch position...
[Page 48] Siemens SIMOTION D425-2
Additional references You will find detailed information on the individual topics in the following table: Table 3-4 References Subject Reference Setting of the operating modes ● SIMOTION SCOUT Configuration Manual Upgrading devices (device update...
[Page 49] Siemens SIMOTION D425-2
3.2.3 RESET button Arrangement The RESET button is located behind the blanking cover on the SIMOTION D4x5‑2. Performing a reset operation A reset causes the entire system to be reset and requires the system to be ramped-up again. It is similar t...
[Page 50] Siemens SIMOTION D425-2
Meaning of the LED displays This table describes the LEDs and their meaning. The PN and SY LEDs have no function for SIMOTION D4x5-2 DP. Table 3-5 Error and status displays LED Meaning RDY Operating states of SIMOTION D incl. SINAMICS Integrate...
[Page 51] Siemens SIMOTION D425-2
Interfaces 4 4.1 Interface overview This section describes the interfaces of the SIMOTION D4x5-2. The position of the interfaces on the module can be found in the following sections: ● Representation of SIMOTION D425-2 DP and D435-2 DP (Page 31)...
[Page 52] Siemens SIMOTION D425-2
Interface Designation Connector type 2. USB interface X135 USB socket Option slot Sockets Note The third port of the PROFINET X150 P3 IO interface has an additional caption for a SIMOTION D4x5-2 DP/PN. It is called X120 PN/IE-OP. This designat...
[Page 53] Siemens SIMOTION D425-2
Position of connectors B A 8 1 Figure 4-1 The position of the DRIVE‑CLiQ interfaces on the D4x5-2 (example of D445-2 DP/PN) Characteristics Table 4-3 DRIVE-CLiQ interface X100 – X105 (D425-2: Only X100 - X103) Characteristic Type Connector ty...
[Page 54] Siemens SIMOTION D425-2
PIN Signal name Signal type Meaning 4 ---- ---- Reserved, do not use 5 ---- ---- Reserved, do not use 6 RXN I Receive data - 7 ---- ---- Reserved, do not use 8 ---- ---- Reserved, do not use A + (24 V) VO Power supply for DRIVE-CLiQ, 450 mA maximum B...
[Page 55] Siemens SIMOTION D425-2
Interface position The following figure contains information on the PROFINET interface of the control unit. Position of the interface, labeling of the ports and the associated displays are described. 'LVSOD\ 6WDWXV JUHHQ 2II \HOORZ 2II 0HDQLQJ...
[Page 56] Siemens SIMOTION D425-2
Interface characteristics Table 4-5 Ports X150 P1 to P3 Characteristic Type Connector type RJ45 socket connector Cable type PROFINET Maximum cable length 100 m Minimum transmission cycle 0.25 ms (D455‑2 DP/PN: 0.125 ms) Autocrossing Yes i.e. bo...
[Page 57] Siemens SIMOTION D425-2
● PROFINET IO controller, I device (also controller and device simultaneously) ● Supports real-time classes of PROFINET IO: – RT (real-time) – IRT (isochronous real-time) The following functions are also supported by Industrial Ethernet: ● ...
[Page 58] Siemens SIMOTION D425-2
4.4 Digital I/Os 4.4.1 Properties Interface characteristics The digital I/Os on the X122, X132 and X142 connectors are for the connection of sensors and actuators. Table 4-7 Wiring of X122, X132 and X142 Features Type Connector type 14-way spri...
[Page 59] Siemens SIMOTION D425-2
Position of connectors The following figure shows the position of the interface connectors on the D4x5-2 and the distribution of the various digital I/Os. �...
[Page 60] Siemens SIMOTION D425-2
352),%86'3 '5,9(&/L4VRFNHW '5,9(&/L4VRFNHW '5,9(&/L4VRFNHW '5,9(&/L4VRFNHW '5,9(&/L4VRFNHW '5,9(&/L4VRFNHW 6,027,21'[...
[Page 61] Siemens SIMOTION D425-2
Interface assignment of X122, X132 and X142 Table 4-8 Digital inputs/outputs X122 Pin Designation 1) Signal type 2) Notes 1 DI 0 I Digital input 0 2 DI 1 I Digital input 1 3 DI 2 I Digital input 2 4 DI 3 I Digital input 3 5 DI 16 I Digital input ...
[Page 62] Siemens SIMOTION D425-2
Pin Designation 1) Signal type 2) Notes 10 DI/DO 13 B Digital input/output 13 (can also be used as input for measuring input or as input for the external zero mark) 11 M GND Ground 12 DI/DO 14 B Digital input/output 14 (can also be used as input f...
[Page 63] Siemens SIMOTION D425-2
Pin Designation 1) Signal type 2) Notes 13 IN/OUT 7 B Digital input/output 7 (can be used as input of a measuring input or output of an output cam) 14 M GND Ground 1) IN/OUT: Bidirectional digital input/output; M: Electronic ground 2) B = Bidire...
[Page 64] Siemens SIMOTION D425-2
DI 0-7, DI 17, DI 18, DI 20, DI 21 (X122, X132) DI/DO 8-15 (X122, X132) IN/OUT 0-7 (X142) Configuration: Assignment Can be configured channel-by-channel on the drive Can be configured channel-by-channel on the drive Can be configured channe...
[Page 65] Siemens SIMOTION D425-2
Features Type Flexible, with wire-end ferrule without plastic sleeve 0.2 mm² … 2.5 mm² Flexible, with wire-end ferrule with plastic sleeve 0.2 mm² … 1.5 mm² AWG / kcmil 22 … 12 Stripped length 6 … 7 mm Tool Screwdriver 0.5 x 3 mm ...
[Page 66] Siemens SIMOTION D425-2
Position of power supply interface 0 -XPSH U 3RZHUVXSSO\FRQQHFWRU Figure 4-5 Position of the power supply interface (example of SIMOTION D445-2 DP/PN) Note The power supply terminal strip must be screwed on tightly using a flat-bladed ...
[Page 67] Siemens SIMOTION D425-2
Position of connectors for SIMOTION D4x5-2 DP The following figure shows the position of the Ethernet interfaces on the D4x5-2 DP and their displays. 'LVSOD\ 'LVSOD\ \HOORZ 2II RUDQJH JUHHQ 2II 'DWDH[FKDQJH 1RGDWDH[FKDQJH 7...
[Page 68] Siemens SIMOTION D425-2
Position of connectors for SIMOTION D4x5-2 DP/PN The following figure shows the position of the Ethernet interfaces on the D4x5-2 DP/PN and their displays. \HOORZ 2II RUDQJH JUHHQ 2II 'DWDH[FKDQJH 1RGDWDH[FKDQJH 7UDQVIHUUDWH�...
[Page 69] Siemens SIMOTION D425-2
Interface characteristics Table 4-14 X127 P1 and X130 P1 (X120 P1 only for SIMOTION D4x5-2 DP) Characteristic Type Connector type RJ45 socket connector Cable type Industrial Ethernet cable ● 4‑ and 8‑wire cables can be used for 10/100 Mbit/s �...
[Page 70] Siemens SIMOTION D425-2
Representati on Pin Assignment in 10/100 Mbit mode Assignment in 1 Gbit mode 8 - - - - - - Reserved, do not use DD- B Bidirectional pair D- I = Input; O = Output; B = Bidirectional 1) Autocrossing functionality (if required, transmit and receive li...
[Page 71] Siemens SIMOTION D425-2
Position of connectors The following figure shows the mounting position and designation of the connectors on the control unit. '303, ;; '3 Figure 4-8 The position of the PROFIBUS X126 a...
[Page 72] Siemens SIMOTION D425-2
Pin Signal name Signal type Meaning 8 1XRS_DP B RS-485 differential signal 9 -- -- Reserved, do not use The 1P5 voltage is provided exclusively for the bus terminal. No OLPs are permitted. Signal type: VO = Voltage output (power supply); O = Output;...
[Page 73] Siemens SIMOTION D425-2
4.8 Slot for CompactFlash card Characteristics Connector type: 50-pin connector This interface should only be used to insert a special SIMOTION CompactFlash card (CF card). &RYHU 6ORWZ LWKLQVHUWHG&)FDUG Figure 4-9 Slot for t...
[Page 74] Siemens SIMOTION D425-2
Interface assignment Table 4-19 Measuring sockets T0, T1, T2 Socket Function Technical specifications 7 7 0 7 T0 Measuring socket 0 Voltage: 0 V to 5 V Resolution: 8 bits Load current: Max. 3 mA Continuous short-circuit-proof Reference ...
[Page 75] Siemens SIMOTION D425-2
4.10 USB interfaces The USB interfaces are used for upgrading the SIMOTION D4x5‑2 via a USB stick. Table 4-20 Interfaces X125 and X135 Characteristics Versions Connector type Double USB socket – type A Version USB 2.0 Power supply 5 V (short-c...
[Page 76] Siemens SIMOTION D425-2
[Page 77] Siemens SIMOTION D425-2
Technical data of the D4x5-2 5 5.1 Shipping and storage conditions Transportation and storage conditions The following conditions apply to modules that are shipped and stored in the original packaging. Table 5-1 Transportation conditions Ty...
[Page 78] Siemens SIMOTION D425-2
Storage of backup batteries Always store backup batteries in a cool and dry place. The batteries have a maximum shelf life of 10 years. Note If you have a spare parts inventory, you must not store a SIMOTION D4x5‑2 with the fan/ battery modul...
[Page 79] Siemens SIMOTION D425-2
Ambient conditions for operation SIMOTION D4x5‑2 can be used under the following ambient conditions: Table 5-2 Environmental requirements Ambient conditions Application range Comments Climatic ambient conditions Climate class 3K3 Acc. to E...
[Page 80] Siemens SIMOTION D425-2
5.3 Dimensions and weights Dimensions and weights Table 5-4 Dimensions and weight of a SIMOTION D4x5‑2 Parameter D425-2 DP D425-2 DP/PN D435-2 DP D435-2 DP/PN D445-2 DP/PN D455‑2 DP/PN Dimensions W x H x D [mm] ● Without fastening using sp...
[Page 81] Siemens SIMOTION D425-2
Table 5-5 Power supply data D425-2 DP D435-2 DP D425-2 DP/PN D435-2 DP/PN D445-2 DP/PN D455‑2 DP/PN Power supply ● Rated value ● Permissible range Safety extra-low voltage DVC A (PELV) 24 VDC (20.4 ... 28.8 V) Current consumption, typically ...
[Page 82] Siemens SIMOTION D425-2
Note If the D4x5‑2 detects undervoltage, the module performs a RESET. If all LEDs are off, either there is no power supply or the voltage level is too low. When the voltage level is in the permissible range again, the D4x5‑2 restarts. Under...
[Page 83] Siemens SIMOTION D425-2
Note The memory sizes may be increased for the current version after the time for going to press for the documentation. The latest values can be found at Internet ( http:// support.automation.siemens.com/WW/view/en/18857317) PLC and motion co...
[Page 84] Siemens SIMOTION D425-2
Data SIMOTION D4x5-2 DP SIMOTION D4x5‑2 DP/PN PROFIBUS interfaces 1) 2 2 PROFINET interfaces 2) --- Onboard: 1 interface with 3 ports Optionally: Second interface with 4 ports via CBE30‑2 1) Supports PROFIBUS DP, isochronous, can be configur...
[Page 85] Siemens SIMOTION D425-2
Digital inputs Table 5-14 Digital inputs on SIMOTION D4x5‑2 Data SIMOTION D4x5-2 Digital inputs 12 ● Rated value 24 V DC ● For signal "1" 15 … 30 V ● For signal "0" 2) -3 … +5 V Galvanic isolation Yes, in groups ...
[Page 86] Siemens SIMOTION D425-2
Data SIMOTION D4x5-2 Switching frequency of the outputs, max. ● With resistive load 4 kHz ● With inductive load 2 Hz ● With lamp load 11 Hz Short-circuit protection yes 1) Specification for Vcc = 24 V, load 48 Ohm, H = 90% V Out ; L = 10% V O...
[Page 87] Siemens SIMOTION D425-2
Further technical data Table 5-16 Fan, non‑volatile data backup, and approvals Data SIMOTION D425-2 DP SIMOTION D425-2 DP/PN SIMOTION D435-2 DP SIMOTION D435-2 DP/PN SIMOTION D445-2 DP/PN SIMOTION D455-2 DP/PN Fan Double fan/battery module is ...
[Page 88] Siemens SIMOTION D425-2
5.7 Clock Properties of the real-time clock The following table lists the properties and functions of the SIMOTION D clock. Table 5-18 Clock properties Properties Meaning Type Hardware clock (integrated "real-time clock") Default set...
[Page 89] Siemens SIMOTION D425-2
5.8 Input and output circuit Protective circuit Figure 5-1 SIMOTION D4x5-2/CX32‑2 input and output circuits Technical data of the D4x5-2 5.8 Input and output circuit SIMOTION D4x5-2 Manual, 04/2014 89 ...
[Page 90] Siemens SIMOTION D425-2
[Page 91] Siemens SIMOTION D425-2
Dimension drawings 6 6.1 D425-2 and D435-2 dimension drawing Figure 6-1 D425-2 and D435-2 dimension drawing SIMOTION D425-2 DP, D425-2 DP/PN, D435...
[Page 92] Siemens SIMOTION D425-2
6.2 D445-2 DP/PN and D455-2 DP/PN dimension drawing Figure 6-2 D445-2 DP/PN and D455-2 DP/PN dimension drawing SIMOTION D445‑2 DP/PN and D455-2 DP/PN m...
[Page 93] Siemens SIMOTION D425-2
6.3 CAD data, dimension drawings, and circuit-diagram macros Dimension drawings and CAD data Dimension drawings, as well as 2D and 3D CAD data can be found: ● In the CAD Creator (http://support.automation.siemens.com/WW/view/en/30559271) ● ...
[Page 94] Siemens SIMOTION D425-2
[Page 95] Siemens SIMOTION D425-2
Supplementary system components 7 7.1 Connection options overview Supplementary system components The following figure shows the connection of the supplementary system components. The connection is: SIMOTION D4x5-2 Manual, 04/2014 95 ...
[Page 96] Siemens SIMOTION D425-2
● Directly on the SIMOTION D module (fan/battery module) ● Via the option slot (TB30, CBE30-2) ● Via the DRIVE‑CLiQ interfaces (Terminal Modules, Control Unit adapter, ...). 7%RU&%( RSWLRQDO 'RXEOH...
[Page 97] Siemens SIMOTION D425-2
7.2 Fan/battery module 7.2.1 Cooling the SIMOTION D4x5-2 and backing up the real-time clock Functions of a fan/battery module The fan/battery module has the following tasks: ● CPU cooling ● Backing up the real-time clock if the SuperCap is insuff...
[Page 98] Siemens SIMOTION D425-2
a malfunction is detected (fan does not turn or fan turns at too low a speed). Cooling clearance NOTICE Higher operating temperature if ventilation clearances are too small The ventilation clearances of 80 mm above and below the components must b...
[Page 99] Siemens SIMOTION D425-2
7.2.2 Installing the fan/battery module Overview The procedure for installing the double fan/battery module is described below. Procedure There are cutouts on the lower side of the control unit to attach the module. Proceed as follows to install ...
[Page 100] Siemens SIMOTION D425-2
Procedure Proceed as follows to replace the battery: 1. Press the latch. This detaches the module from its front latching device. 3UHVVXU HRQODWFK Figure 7-3 Unlatch the double fan/battery module 2. Tilt the double fan/battery module forwar...